FLN36-12D saklar beban AC voltase dhuwur njero ruangan minangka switchgear voltase medium sing dikembangake dening perusahaan kita kanthi referensi teknologi anyar internasional lan miturut standar sing cocog karo sistem tenaga negaraku.2004 "3.6kV-40.5kV High Voltage AC Load Switch", GB1985-2004 "High Voltage AC Isolation Switch and Earthing Switch", GB / T11022-1999 "Common Technical Requirements for High Voltage Switchgear and Control Equipment Standards", minangka standar saka kabinet jaringan ring.elemen switching utama.Saklar beban minangka switchgear voltase medium multi-fungsi sing nggabungake gerbang, bukaan lan grounding.Iki kapenuhan gas SF6 saka 0.05MPa ing cangkang resin epoksi sing disegel kanthi struktur sing dikuatake, lan ing ndhuwur digayuh kanthi bagean paling sithik.Telung fungsi njamin kualitas produk lan nambah linuwih.Pangopènan-free, operasi aman kanggo luwih saka 20 taun ing kahanan normal.

Gunakake Kahanan Lingkungan

a) Ketinggian ora ngluwihi 1000m;
b) Suhu udara sekitar: wates ndhuwur +40, watesan ngisor -25ºC;
c) Kelembapan relatif: rata-rata saben dina ora luwih saka 95%, lan rata-rata saben wulan ora luwih saka 90%;
d) Udhara ing saubengé ora temenan kacemar gas korosif utawa gas sing bisa diobong, uap banyu, lsp;
e) Ora ana getaran sing kerep banget.

Parameter Teknis Utama

Proyek

Unit

data

Dirating voltase

kV

12

Frekuensi dirating

Hz

50

Rated saiki

A

630

Rated puncak tahan saiki

kA

50

4s dirating short-time tahan saiki

20

Rated nggawe saiki

50

Rated breaking saiki

Arus beban aktif

A

630

Arus pemutus loop tertutup

630

Kabel charging breaking current

10

Frekuensi daya tahan voltase 1min gantian, menyang lemah / fraktur

kV

42/48

Impuls kilat tahan voltase phase-to-phase, menyang lemah / fraktur

75/85

Tekanan relatif gas SF6 (20 ℃ tekanan gauge)

MPa

≤0.04

Rated tegangan operasi (listrik)

v

AC/DC220

Tegangan dirating shunt release

AC/DC220

kacepetan mbukak rata-rata

m/s

3.5±1.5

Kacepetan nutup rata-rata

m/s

3.5±1.5

Telung fase mbukak lan nutup sinkronisasi

ms

≤3

Resistance sirkuit utama

uQ

≤120

Operasi manual torsi maksimum

Nm

160

Jarak pusat fase

mm

210±0.5